Ontario Building Code Warranted by Tarion

By law, all new homes in Ontario built by a licensed vendor or builder come with a statutory warranty under the Ontario New Home Warranties Plan Act (ONHWPA). This statutory warranty protection follows the home and is valid for seven years from the original date of possession, regardless of who owns the home. Coverage for Ontario Building Code (OBC) violations is as follows:

  • Violations of the OBC are covered for one year from the original date of possession
  • Violations of the OBC related to health and safety are covered for two years from the original date of possession

In an effort to improve coordination with municipal building departments, Tarion will now be posting on a quarterly basis a summary of any claims that were deemed warranted and were related to the OBC. This information is being provided to allow building departments an opportunity to better understand the issues that are brought to Tarion's attention after an occupancy permit is granted.

To view the claims by quarter, click on the accordion menus below. If you have any questions regarding this information, please email municipalinfo@tarion.com(link sends email)

Individual emails will go out to municipal building departments on a quarterly basis with information on the warranted OBC deficiencies, if any, in that municipality. To facilitate this outreach, please complete this form(link is external) with the contact information for the person who should receive this emailed information.

2024 OBC Deficiencies

Q1
Description of OBC Deficiency
Tarion warranted a Carbon Monoxide Alarm not in compliance with 9.33.4. Carbon Monoxide Alarms.
Tarion warranted columns not in compliance with 9.17.4.3. Columns in Contact with Concrete.
Tarion warranted missing weep holes not in compliance 9.20.13.8. Required Weep Holes.
Tarion warranted an attic hatch not in compliance with 9.25.3.3. Continuity of the Air Barrier System.
Tarion warranted dryer ventilation ducts not in compliance with 9.32.1.4. Venting of Laundry-Drying Equipment.
Tarion warranted guards not in compliance with 9.8.8.1. Required Guards.
Tarion warranted guards not in compliance with 9.8.8.1. Required Guards.
Tarion warranted an exhaust not in compliance with 9.32.3.5. Supplemental Exhaust.
Tarion warranted gas proofing not in compliance with 9.10.9.16. Separation of Storage Garages.
Tarion warranted insulation not in compliance with 9.25.2.3. Installation of Thermal Insulation. 
Tarion warranted a duct not in compliance with 9.32.3.10. Ducts.
Tarion warranted brick veneer not in compliance with 9.20.12.3. Corbelling for Masonry Veneer.
Tarion warranted tiles not in compliance with 9.29.10.4 Moisture Resistant Backing.
Tarion warranted a missing guard not in compliance with 9.8.8.1. Required Guards.
Tarion warranted a sump pump not in compliance with 9.25.3.3. Continuity of the Barrier System.
Tarion warranted a landing not in compliance with 9.8.6.2. Required Landings.
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes.
Tarion warranted a handrail not in compliance with 9.8.7.2. Continuity of Handrails.
Tarion warranted sealant not in compliance with 9.27.4.1. Required Sealants.
Tarion warranted weather stripping not in compliance with 9.7.3. Performance of Windows, Doors and Skylights.
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads.
Tarion warranted a door not in compliance with 9.10.9.16. Separation of Storage Garages.
Q2
Description of OBC Deficiency
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads.
Tarion warranted grade not in compliance with 9.15.4.6. Extension Above Ground Level.
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads.
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads.
Tarion warranted a handrail not in compliance with 9.8.7.7. Design and Attachment of Handrails.
Tarion warranted masonry not in compliance with 9.20.12.3. Corbelling for Masonry Veneer.
Tarion warranted handrails not in compliance with 9.8.7.7. Design and Attachment of Handrails.
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes.
Tarion warranted flashing not in compliance with 9.20.13.5. Flashing for Weep Holes in Masonry Veneer.
Tarion warranted a garage floor not in compliance with 9.35.2.2. Garage Floor.
Tarion warranted fire sealant not in compliance with 3.1.9.1. Fire Stops.
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of the Air Barrier System.
Tarion warranted spray foam not in compliance with 9.10.17.10. Protection of Foamed Plastics.
Tarion warranted stairs not in compliance with 9.8.4.4. Uniformity and Tolerance for Risers, Runs and Treads.
Tarion warranted a trap not in compliance with 7.4.5.5. Trap Seals.
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops.
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops.
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops.
Tarion warranted guards not in compliance with 9.8.8.5. Opening in Guards.
Tarion warranted an air barrier not in compliance with 9.10.9.16. Separation of Storage Garages.
Tarion warranted a door not in compliance with 9.10.13.15. Doors Between Garages and Houses or Dwelling Units.
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of the Air Barrier System.
Tarion warranted a backflow preventer not in compliance with 7.6.2.2. Back-Siphonage.
Q3
Description of OBC Deficiency
Tarion warranted guards not in compliance with 9.8.8.1 ‘Required Guards’
Tarion warranted joints between tiles and bathtub not in compliance with 9.29.10.5. ‘Joints between tiles and Bathtub’
Tarion warranted an air barrier not in compliance with 9.25.3 "Continuity of the Air Barrier System"
Tarion warranted heating design and installation not in compliance with 9.33.1.1. ‘Design and Installation Requirements’
Tarion warranted steps not in compliance with 9.8.4.1 ‘Dimensions for Risers’
Tarion warranted weep holes not in compliance with 9.20.13.8.(1) ‘Required Weep Holes’
Tarion warranted clearance from grade not in compliance with 9.15.4.6.(1) ‘Extension Above Grade Level’
Tarion warranted spindles not in compliance with 9.8.8.5 (3) ‘Openings in Guards’
Tarion warranted roof drainage not in compliance with 5.6.2.2.(3) ‘Accumulation and Disposal’
Tarion warranted fire ratings not in compliance with 9.10.3.1 ‘Fire-Resistance and Fire Protection Ratings’
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’
Tarion warranted entrance lighting not in compliance with 9.34.2.1 ‘Lighting of Entrances’
Tarion warranted lateral support not in compliance with 9.17.2.2.(1) ‘Lateral support’
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’
Tarion warranted a shut-off valve not in compliance with 7.6.1.3. ‘Control and Shut-off Valves’
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’
Tarion warranted a pool deck not in compliance with 3.11.3.1.(24) ‘Pool and Pool Design and Construction Requirements
Tarion warranted a stud wall not in compliance with 3.8.3.13(2)(e) ‘Stud Wall Reinforcement’
Tarion warranted entry door not in compliance with 3.8.1.3. ‘Barrier-Free Path of Travel’
Tarion warranted lighting not in compliance with 12.2.4.1. ‘Motion Sensors’
Tarion warranted lighting not in compliance with 12.2.4.1. ‘Motion Sensors’
Tarion warranted a toilet not in compliance with 3.8.3.8. ‘Washroom to be Barrier-Free’
Tarion warranted a door not in compliance with 3.8.3.3. ‘Doorways and Doors’
Tarion warranted a door not in compliance with 3.8.3.3. ‘Doorways and Doors’.
Tarion warranted a water closet not in compliance with 3.8.3.8 ‘Water Closet Stalls and Enclosures’
Tarion warranted backflow prevention not in compliance with 7.6.2.2. ‘Back-Siphonage’
Tarion warranted a door not in compliance with 9.10.13.15 ‘Other Requirements for Windows and Doors’
Tarion warranted a guard not in compliance with 9.8.8.5 ‘Openings of Guards’
Tarion warranted a sump pit not in compliance with 9.25.3.3. ‘Sump Pits’
Tarion warranted a window height not in compliance with 9.15.4.6 ‘Extension Above Ground Level’
Tarion warranted the first plane of protection not in compliance with 9.27.2.3 ‘First and Second Planes of Protection’
Tarion warranted a door not in compliance with 9.7.3.1 ‘Performance of Windows, Doors and Skylights’
 

2023 OBC Deficiencies

Q1
Description of OBC Deficiency
Tarion warranted a stair-related claim where the front steps to the house were not in compliance with 9.8.4.4.(1). Uniformity and Tolerances for Riser, Runs and Treads. 
Tarion warranted a claim related to a factory-built fireplace where its installation was not in compliance with 9.22.8.1. Conformance to Standard CAN/ULC-S610-M. 
Tarion warranted a cladding related claim where the first plane of protection for the exterior wall was not in compliance with 9.27.2.3. First and Second Planes of Protection. 
Tarion warranted a drainage related claim where the foundation wall was not in compliance with 9.14.2.1. Foundation Wall Drainage. 
Tarion warranted a claim related to missing guards and missing handrails from a rear deck and stairs (serving deck). These items are not in compliance with 9.8.8.1. Required Guards, and 9.8.7.1. Required Handrails. 
Tarion warranted a mechanical ventilation related claim where the air intake for the furnace and water heater were not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings. 
Tarion warranted a thermal insulation related claim where the installation in the basement level was not in compliance with 9.25.2.3. Installation of Thermal Insulation. 
Tarion warranted a cladding related claim where the brick veneer installed was not in compliance with 9.20.12.3. Corbelling for Masonry Veneer. 
Tarion warranted a heating related claim where the installed system was not able to maintain an indoor temperature in accordance with 9.33.3.1. Indoor Design Temperatures. 
Tarion warranted a guard related claim where the front porch of the house was not in compliance with 9.8.8.1. Required Guards. 
Tarion warranted an electrical related claim where the utility room was not in compliance with 9.34.2.2. Lighting Outlets in Houses and Dwelling Units.
Tarion warranted a cladding related claim where the vents penetrating the cladding were not sealed in accordance with 9.27.4.1. Required Sealants. 
Tarion warranted a claim related to wall tile finishes where the joints between the washroom tiles were not in compliance with 9.29.10.5. Joints Between Tiles and Bathtub. 
Tarion warranted a plumbing related claim where the water pipe was not in compliance with 7.3.4. Support of Piping. 
Q2
Description of OBC Deficiency
Tarion warranted a handrail not in compliance with 9.8.7.7.  Design and Attachment of Handrails. 
Tarion warranted insulation not in compliance with 9.25.2.1. Required Insulation. 
Tarion warranted intake and exhaust pipes not in compliance with 9.32.3.12.  Outdoor Intake and Exhaust Openings.
Tarion warranted an exterior step not in compliance with 9.8.4.4.  Uniformity and Tolerances for Riders, Runs and Treads. 
Tarion warranted an exterior door not in compliance with 9.25.1.1. Heat Transfer, Air Leakage and Condensation Control - Scope and Application. 
Tarion warranted an air barrier not in compliance with 9.10.9.16.  Separation of Storage Garages. 
Tarion warranted a balcony guardrail and not in compliance with 9.8.8.1. Required Guards.
Tarion warranted tread depth not in compliance with Table 9.8.4.1., 9.8.4.4. and 9.8.2.2. Dimensions for Risers, Uniformity and Tolerances for Risers, Runs and Treads, and Height Over Stairs. 
Tarion warranted rise of a step not in compliance with 9.8.4.1. Dimensions for Risers. 
Tarion warranted radon mitigation not in compliance with 9.13.4.1. and 9.13.4.2. Soil Gas Control. 
Tarion warranted a foundation not in compliance with 9.25.  Heat Transfer, Air Leakage and Condensation Control.
Tarion warranted a self-closer device not in compliance with 9.10.13.10. Self-Closing Devices. 
Tarion warranted a window installation not in compliance with 9.7.6.2. and 9.25.3.3. Sealants, Trim and Flashing and Continuity of Air Barrier System. 
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of Air Barrier System.
Tarion warranted wood framing not in compliance with 9.27.1.1.  Cladding – General. 
Tarion warranted vapour barrier not in compliance with 9.13.2.5. Moisture Protection for Interior Finishes. 
Tarion warranted an air barrier not in compliance with 9.10.9.16. and 9.25.3.1. Separation of Storage Garages and Required Barrier to Air Leakage. 
Tarion warranted weep holes within the masonry not in compliance with 9.20.13.8.  Required Weep Holes. 
Tarion warranted an HVAC duct not in compliance with 6.2.4.3.  Construction and Installation of Ducts and Plenums. 
Tarion warranted framing not in compliance with 9.23.10.1 and 9.23.12.1.  Stud Size and Spacing and Openings in Non-Loadbearing Walls. 
Tarion warranted a basement foundation that had a form tie not in compliance with 9.15.6.3.   Form Ties. 
Tarion warranted weep holes within the masonry not in compliance with 9.20.13.8.  Required Weep Holes. 
Tarion warranted a guard not in compliance with 9.8.8.2.  Loads on Guards. 
Tarion warranted a steel lintel not in compliance with 9.20.5.2. Lintels or Arches. 
Tarion warranted vent opening not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings.
Tarion warranted an air barrier not in compliance with 9.25.3.1. and 9.25.3.3.  Required Barrier to Air Leakage and Continuity of the Air Barrier System.
Tarion warranted a landing not in compliance with 9.8.6.3. Dimensions of Landings. 
Q3
Description of OBC Deficiency 
Tarion warranted front porch guard rails not in compliance with 9.8.8.1. Required Guards.
Tarion warranted primary entrance doors not in compliance with 9.7.2.1. Entrance Door.
Tarion warranted Basement - Stairs - Staircase/Steps - Stairs leading to basement not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers and Treads.
Tarion warranted hot water heater input and exhaust pipes not in compliance with 9.32.3.12. Outdoor Intake and Exhaust
Openings.
Tarion warranted stairs not in compliance with 9.8.4.1. Uniformity and Tolerances for Risers and Treads.
Tarion warranted man doors to garages not in compliance with 9.10.13.15 (1). Doors Between Garages and Dwelling Units
Tarion warranted weeping holes not in compliance with 9.20.13.8 (1)(b). Required Weep Holes.
Tarion warranted drywall not in compliance with 9.10.9.16.(4)(a). Separation of Storage Garages
Tarion warranted hot water supply; not in compliance with 9.31.3.2(2). Required Connections.
Tarion warranted door frame not in compliance with 9.10.9.16.(4)(a). Separation of Storage Garages
Tarion warranted a deck railing not in compliance with 9.8.8.1. Required Guards.
Tarion warranted electrical wires not in compliance with 9.34.1.5 (1). Wiring and Cables.
Tarion warranted steps not in compliance with 9.8.9.2 (1). Exterior Concrete Stairs.
Tarion warranted a sump pump pit not in compliance with 9.25.3.3.(16). Continuity of Air Barrier.
Tarion warranted a floor drain not in compliance 9.31.4.4.(1). Floor Drains.
Tarion warranted steps not in compliance with 9.8.1.2. (1). Exit Stairs, Ramps and Landings.
Tarion warranted steps not in compliance with 9.8.1.2. (1). Exit Stairs, Ramps and Landings.
Tarion warranted electrical wires not in compliance with 9.34.1.5 (1). Wiring and Cables.
Tarion warranted a front door not in compliance with 9.7.2.1. Entrance Door.
Tarion warranted support timbers not in compliance with 9.23.5.3. Wall Studs.
Q4
Description of OBC deficiency
Tarion warranted steps not in compliance with 9.8.4.4.  Uniformity and Tolerances for Risers and Treads.
Tarion warranted a basement floor slab not in compliance with 9.23.2.3.  Protection from Dampness. 
Tarion warranted a staircase not in compliance with 9.8.2.1. Stair Width.
Tarion warranted trimmer joists not in compliance with 9.23.9.6. Trimmer Joists.
Tarion warranted framing not in compliance with 9.23.9.4.  Strapping and Bridging. 
Tarion warranted window openings not in compliance with 9.23.12.2.  Openings in Load Bearing Walls. 
Tarion warranted floor joists not in compliance with 9.23.9.4. Strapping and Bridging.
Tarion warranted window openings not in compliance with 9.23.12.2. Openings in Load Bearing Walls.
Tarion warranted a door opening not in compliance with 9.23.9.6. Trimmer Joists.
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control.  
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes.
Tarion warranted an exterior door not in compliance with 9.25.3.3 and 9.25.4.1. Continuity of the Air Barrier System and Required Barrier to Vapour Diffusion.
Tarion warranted a vent not in compliance with 9.19.1.2. Vent Requirements. 
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted a door not in compliance with 9.10.13.15.  Doors Between Garages and Houses or Dwelling Units. 
Tarion warranted a roof not in compliance with 9.26.3.1. Slope.
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. 
Tarion warranted brick masonry not in compliance with 9.20.12.3. Corbelling for Cavity Walls. 
Tarion warranted a roof not in compliance with 9.26.3.1.   Slope.
Tarion Warranted a guard not in compliance with 9.8.8.4. Guards for Floors and Ramps in Garages.
Tarion warranted an HVAC vent not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. 
Tarion warranted a door not in compliance with 3.1.8.5.  Installation of Closures. 
Tarion warranted a staircase and landing not in compliance with 3.4.6.3.  Maximum Vertical Rise of Stair Flights and Required Landings. 
Tarion warranted ventilation not in compliance with 6.2.2.3 and 6.2.3.8.  Ventilation of Storage and Repair Garages and Exhaust Ducts and Outlets. 
Tarion warranted staircase levels; not in compliance with 3.4.6.8.  Treads and Risers. 
Tarion warranted an exit not in compliance with 3.4.3.5.  Headroom Clearance. 
Tarion warranted a landing not in compliance with 3.4.6.4.  Dimensions of Landings. 
Tarion warranted vent covers missing to open and close vents; not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops.
Tarion warranted a garage door not in compliance with 9.10.13.15.  Doors Between Garages and Houses or Dwelling Units.
Tarion warranted a staircase and handrail not in compliance with 9.8.4.5A. and 9.8.7.4.  Spiral Stairs and Height of Handrails.
Tarion warranted a foundation not in compliance with 9.15.4.6. Extension Above Ground Level. 

2022 OBC Deficiencies

Q1
Description of deficiency
Tarion warranted a claim related to exterior face brick overhanging a foundation wall on a house of over 25 mm house in contravention with Sentence 9.20.12.3.(1).  
Tarion warranted a claim related to a lack of backdrafts to two exhaust vents on a house in contravention with Sentence 6.2.4.11.(2).  
Tarion warranted a claim where there was dampproofing membrane missing on a foundation wall, below grade, to house in contravention with OBC Sentence 9.13.2.5.(1)  
Tarion warranted a claim with respect to a door leading to an attached garage from the house was not tightly fitted in accordance with Sentence 9.10.13.15.(1).  
Tarion warranted a claim with respect to an exterior guard on a house that had openings greater than a 100 mm sphere in contravention with OBC Sentence 9.8.8.5.(1)  
Tarion warranted a claim with respect to a lack of exterior caulking around window frames and other penetrations to the exterior wall of a house in contravention with OBC Article 9.27.4.1.  
Tarion warranted a claim with respect to a sliding door that opens onto a drop in elevation of 1 m not protected with a guard or a system to reduce the door opening to not more than 100 mm to a house in contravention with OBC Sentence 9.8.8.1.(4).  
Tarion warranted a claim with respect to an attached garage floor that did not drain to the exterior in contravention with OBC Sentence 9.35.2.2.(1).  
Tarion warranted a claim with respect a door closer to a door between a house and an attached garage as not closing the door as requited in contravention with OBC Sentence 9.10.13.15.(1).  
Tarion warranted a claim with respect to an exterior landing to a house that had an adjacent drop of 1.25 m in contravention of OBC Clause 9.8.8.1.(1)(b).  
Tarion warranted a claim with respect to a kitchen exhaust duct in a house that did not discharge directly to the outdoors in contravention with OBC Sentence 6.2.4.11.(4).  
Tarion warranted a claim with respect to a kitchen exhaust duct diameter in a house that was undersized in contravention with Sentence 9.32.3.5.(4).  
Tarion warranted a claim with respect to a lack of a handrail to stairs in a garage to a house in contravention with OBC Sentence 9.8.7.1.(4)  
Tarion warranted a claim with respect to the lack of a guard to the front porch to a house where the difference between the porch elevation and the adjacent ground was greater than 600 mm in contravention of OBC Sentence 9.8.8.1.(1).  
Tarion warranted a claim with respect to a smoke alarm in the basement of a house door was not working when tested in contravention with OBC Sentence 9.10.19.3.(1).  
Tarion warranted a claim with respect to an air barrier system in the basement of a house was not sealed in contravention with OBC Sentence 9.25.3.3.(1).  
Tarion warranted a claim with respect to exhaust ducts in a house that were discharging into an attic in contravention of OBC Sentence 9.32.3.10.(2).  
Tarion warranted a claim with respect to weatherstripping that did not seal an attic hatch in contravention of OBC Sentence 9.25.3.3.(13).  
Tarion warranted a claim that the attached garage in a house was did not provide the required gas proofing in contravention of OBC 9.10.9.16.(4).  
Tarion warranted a claim with respect to two windows in a house that were not easily operable in contravention with OBC Clause 9.7.3.1.(1)(f).  
Tarion warranted a claim with respect to rigid insulation on a house was exposed to the elements in contravention with OBC Sentence 9.25.2.3.(6).  
Tarion warranted a claim that the air barrier installed behind a gas fireplace in a house was not sealed in contravention of OBC 9.25.3.3.(3).  
Tarion warranted a claim with respect to the installation of a vapour barrier installed between joists in a house that was not in compliance with OBC Sentence 9.25.4.1.(1).    
Tarion warranted a claim where the anchor bolts in an attached garage were not bolted down securely in contravention with OBC Sentence 9.23.6.1.(3).  
Tarion warranted a claim that cut or notched joists in an attached garage of a house were in contravention with OBC Sentence 9.23.5.2.(1).  
Tarion warranted a claim that the openings in a guard on an exterior deck were greater than a 100 mm sphere in contravention with OBC Sentence 9.8.8.5.(1)  
Tarion warranted a claim with respect to an exterior stair to a house that exceeded maximum tolerances for risers in OBC Sentence 9.8.4.4.(1).  
Tarion warranted a claim with respect to an interior stair tread to a house that was less then the minimum length in contravention of OBC Sentences 9.8.4.2.(1) and 9.8.4.4.(3).  
Tarion warranted a claim with respect to an interior stair in a house that had risers in excess of 200 mm in contravention with OBC Table 9.8.4.1.  
Tarion warranted a claim with respect to a missing S/A outlet in a house in contravention with OBC Sentence 6.2.4.4.(1).  
Tarion warranted a claim with respect a door closer to a door between a house and an attached garage as not closing the door as requited in contravention with OBC Sentence 9.10.13.15.(1).  
Tarion warranted a claim with respect to the lack of a guard to a stair to the basement of a house in contravention with OBC Sentence 9.8.8.1.(3).  
Tarion warranted a claim with respect to an exterior stair to a house that exceeded maximum tolerances for risers in OBC Sentence 9.8.4.4.(1).  
Tarion warranted a claim with respect to a shower stall in a house that had its walls not in compliance with OBC Sentences 9.29.2.1.(1) and 9.29.10.5.(1).  
Tarion warranted 3 claims with respect to 3 doors to a house that were not sealed in contravention with OBC Sentence 9.7. 3.1.(1).  
Tarion warranted a claim with respect to a lack of a sufficient gas barrier between an attached garage and the house in contravention of Sentence 9.10.9.16.(4).  
Tarion warranted a claim with respect to an exterior guard to a deck that was not fastened correctly in contravention with OBC Table 9.8.8.2.  
Tarion warranted a claim with respect to the construction of an exterior wooden deck at the rear of a home where the following deficiencies were identified: The ledger board supporting the joists was not fastened to the frame of the house in contravention with OBC Sentence 9.23.6.1.(1), An 8 ply built-up beam were not nailed together in contravention of OBC Sentence 9.23.8.3.(7).  
Tarion warranted a claim with respect to an exterior stair that had a riser height greater than 200 mm in contravention of OBC Table 9.8.4.1.  
Tarion warranted a claim with respect to an exterior stair that had a riser height greater than 200 mm in contravention of OBC Table 9.8.4.1.  
Tarion warranted a claim with respect a door closer to a door between a house and an attached garage as not closing the door as requited in contravention with OBC Sentence 9.10.13.15.(1).  
Tarion warranted a claim with respect to and exterior stair to a house that had 2 of its treads with a negative slope in contravention with OBC Sentence 9.8 4.4.(5).  
Tarion warranted a claim with respect to a soil waste pipe in a house that was not protected from frost in contravention with OBC Sentence 7.3.5.4.(1).  
Tarion warranted a claim with respect to built up wood beam in a house that was not nailed together in contravention with OBC Sentence 9.23.8.3.(7).  
Tarion warranted a claim with respect to lack of an air barrier to a cold room in a house in contravention with OBC Sentence 9.25.3.1.(1).  
Tarion warranted a claim with respect to insufficient clearance between a supply air plenum in a house in contravention with OBC Sentence 6.2.4.10.(3).  
Tarion warranted a claim with respect to a cold room door frame in a house that was not sealed to the air-barrier in contravention of OBC Sentence 9.7.6.1.(3).  
Q2
Description of deficiency
Tarion warranted a claim related to a sump pit lid in a house that was not sealed in contravention with Sentence 9.14.5.2.(2).
Tarion warranted a claim related to a missing warm air supply duct in a bathroom in a house in contravention with Sentence 6.2.4.4.(1).
Tarion warranted multiple claims to a multi-residential building where there was a lack of fire stopping material to piping penetrations in contravention with OBC Sentence 3.1.9.1.(1)
Tarion warranted a claim in a multi-residential building where a vertical fire separation was not terminated with smoke tight joints at the intersection of the fire separation and the floor in contravention with Sentence 3.1.8.3.(2).
Tarion warranted a claim with respect to a clothes washer standpipe drain in a house that is less than 600 mm in length in contravention with OBC Sentence 7.4.9.3.(2)
Tarion warranted a claim with respect to a lack of a drip edge to an exterior door sill to a house in contravention with OBC Article 9.20.13.12.
Tarion warranted a claim with respect to a  wood column, to a house, supporting an exterior deck that had twisted to the extent that the 2 ply beam supported on the column has insufficient lateral support in contravention with OBC Sentence 9.17.2.2.(2).
Tarion warranted a claim in a multi-residential building with respect to a concrete block wall fire separation that had multiple cracks in the wall in contravention with OBC Sentence 3.1.8.1.(1).
Tarion warranted a claim to a multi-residential building where there was a lack of fire stopping material to a sprinkler piping penetration in contravention with OBC Sentence 3.1.9.1.(1)
Tarion warranted a claim to a multi-residential building where a drywall horizontal ceiling fire separation was not constructed with smoke tight joints in contravention of OBC Sentence 3.1.8.3.(2).
Tarion warranted a claim to a multi-residential building where the exterior insulated finish system (EIFS) did not have drainage to the exterior in multiple locations in contravention with OBC Sentence 5.6.2.1.(2).
Tarion warranted a claim to a multi-residential building where the municipality identified that a reduced pressure zone backflow preventor is required to be installed instead of a double check valve to a snow melt system in contravention with OBC Sentence 7.6.2.2.(2).
Tarion warranted a claim to a multi-residential building where a door leading out of a stair did not provide the required clearances as required by OBC Sentence 3.8.3.3.(10).
Tarion warranted a claim to a multi-residential building where there was a lack of fire stopping material around a pipe that  penetrated a required fire separation in contravention with OBC Sentence 3.1.9.1.(1). 
Tarion warranted a claim where a vent to a cold cellar on a house was not adequately sealed in contravention with OBC Sentence 9.27.4.1.(1).
Tarion warranted a claim with respect to a smoke/carbon monoxide alarm in a house that was not securely fastened to the ceiling in in contravention with OBC Sentence 9.10.19.(1).
Tarion warranted a claim with respect to the lack of a guard to the front porch to a house where the difference between the porch elevation and the adjacent ground was greater than 600 mm in contravention of OBC Sentence 9.8.8.1.(1).
Tarion warranted a claim that the openings in a guard on an exterior front porch were greater than a 100 mm sphere in contravention with OBC Sentence 9.8.8.5.(1).
Tarion warranted a claim that the joints in the flashing on a parapet to a flat roof to a house was not sealed in contravention of OBC 9.20.13.7.(4).
Tarion warranted a claim with respect to a window in a house that was required to have a guard or be limited in opening not more than a 100 mm sphere in contravention with OBC Sentence 9.8.8.1.(6).
Tarion warranted a claim with respect to joists framed into a header joist that was not provided with joist hangers in contravention with OBC Sentence 9.23.9.7.(1).
Tarion warranted a claim with respect to the lack of a guard to the front porch to a house where the difference between the porch elevation and the adjacent ground was greater than 600 mm in contravention of OBC Sentence 9.8.8.1.(1).
Tarion warranted a claim that joist hangers, in a house, were not fastened in accordance with the manufacturer’s instructions and in contravention with OBC Sentence 9.23.9.2.(2).
Tarion warranted a claim with respect to a lack of weep holes to face brick on a house in contravention with OBC Sentence 9.20.13.8.(1)
Tarion warranted a claim with respect to the thickness of mortar joints of face brick being in excess of the tolerances provided in Sentence 9.20.4.1.(2).
Tarion warranted a claim with respect to an interior stair to a house that had a headroom clearance from the stair to a bulkhead of less than 1950 mm in contravention of OBC Sentences 9.8.2.2.(3).
Tarion warranted a claim related to exterior stone masonry face brick overhanging a foundation wall on a house of over 25 mm in contravention with Sentence 9.20.12.3.(1).
Tarion warranted a claim with respect to an interior stair to the basement stair to a house that exceeded maximum tolerances for risers in OBC Sentence 9.8.4.4.(1).
Tarion warranted a claim with respect to a smoke alarm in a house that was missing in one of the bedrooms in contravention with OBC 9.10.19.3.(1).
Tarion warranted a claim with respect to an exterior front door to a house that was not sealed in contravention with OBC Sentence 9.7. 3.1.(1).
Tarion warranted a claim with respect to the lack of heating to a walk-in closet in a house that would not heat to the minimum value of 22 °C in contravention with OBC 9.33.3.1.(1)
Q3
Description of deficiency
Tarion warranted a structural related claim where the lateral support of a basement column was not in compliance with 9.17.2.2.(1).
Tarion warranted an HVAC related claim where the exhaust outlets had missing corrosion-resistant screens as per 6.2.3.12.(3).
Tarion warranted a roofing related claim where there was inadequate drainage/slope on the roof affecting the supported guard posts as per 9.26.3.1.(4).  
Tarion warranted a guard related claim where the deck guards were not in compliance with 9.8.8.5. “Opening in Guards”.  
Tarion warranted a fire separation related claim where the door between the garage and the house had no self-closing device as per 9.10.13.15.(1)
Tarion warranted a surface drainage related claim where the window well did not drain in accordance with 9.14.6.3.(1) and allowed water penetration into the building envelope.
Tarion warranted a handrail related claim where the exterior stairs did not have handrails as per 9.8.7. requirements.
Tarion warranted a guard related claim where a deck was built with no guards and in contravention of 9.8.8.
Tarion warranted a stairs related claim at the mechanical room entrance, where the riser was not in compliance with 9.8.4.1.
Tarion warranted an insulation related claim where the installation of the spray foam insulation on an exterior wall was not in compliance with 9.25.2.3.
Tarion warranted a stairs related claim where the entrances (front and back) to the house had risers in excess of 9.8.4.1.
Tarion warranted a masonry related claim where the mortar joints were not in compliance with 9.20.4.1.
Tarion warranted a fire separation related claim where the door between the garage and the house did not have a working self-closing device as per 9.10.13.15.(1).
Tarion warranted a structural related claim where the porch columns were not installed in accordance with 9.17.2.2. for lateral support, and 9.17.4.3. for separation from concrete in contact with the ground.
Tarion warranted a flooring related claim where the finished flooring surface was not smooth and free of open defects as required by 9.30.1.4.
Tarion warranted a hallway related claim where the width was not in accordance with 9.5.10.1.
Tarion warranted a handrail related claim where the stairs from the garage leading to the house were not in compliance with 9.8.7.1.
Tarion warranted a window installation claim where the window was not sealed to the vapour and air barrier as per 9.7.6.1.
Tarion warranted a guard and handrail related claim for the front porch and stairs not in compliance with 9.8.8.1. and 9.8.7.1.
Tarion warranted an air barrier related claim where the sump pit was not sealed in accordance with 9.15.5.2.(2)(b) and 9.25.3.3.(16).
Tarion warranted a fire separation related claim where the door between the garage and the house had no self-closing device as per 9.10.13.15.(1)
Tarion warranted a fire separation related claim where the air barrier in the attached garage did not provide an effective gasproofing barrier as per 9.10.9.16.(4).
Tarion warranted a stair related claim where the riser was not in compliance with 9.8.4.1.
Tarion warranted a fire separation related claim where the door between the attached garage and the house did not provide an effective gasproofing barrier in accordance with 9.10.13.15.
Tarion warranted an HVAC related claim where the warm air supply outlets in the kitchen were not provided with diffusers and adjustable openings as per 6.2.4.4.(9).
Tarion warranted a structural related claim where several basement columns were resting on concrete without any protection from dampness as required by 9.23.2.3.
Tarion warranted a fire separation related claim where the air barrier in the attached garage did not provide an effective gasproofing barrier as per 9.10.9.16.(4). Two areas in the ceiling drywall had missing seams.
Tarion warranted a claim
Tarion warranted a stair related claim where the treads for the front porch stairs were not in compliance with 9.8.4.4.
Tarion warranted a lighting related claim where no light fixture was installed in the laundry room as required by 9.34.2.2.
Tarion warranted a ventilation related claim where the furnace exhaust outlet in the rooftop did not have a mesh screen cover as per 9.32.3.12.  
Tarion warranted a flooring related claim where the furnace/water heater room had a section of exposed unfinished floor with no water resistant material as per 9.30.1.2.
Tarion warranted a stair related claim where the risers were not in compliance with 9.8.4.1.
Tarion warranted a soil gas (radon) related claim , where the floor assembly in contact with the ground was not constructed to resist the leakage of soil gas from the ground into the building as per 9.13.4.2.
Tarion warranted a guard related claim where the required front porch guards had a gap between the brick column and the guard post in excess of 9.8.8.5.
Q4
Description of OBC Deficiency
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32.
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit was not tight-fitting as per 9.10.13.15.(1) 
Tarion warranted a handrail related claim where its construction was not in compliance with 9.8.7.2. Continuity of Handrails. 
Tarion warranted a guard related claim for the basement stairs where the guards were not in compliance with 9.8.8.1. Required Guards. 
Tarion warranted a ventilation related claim where the kitchen exhaust was not in compliance with 9.32.3.
Tarion warranted a fire protection related claim for the ICF foundation wall not in compliance with 9.10.17.10. Protection to Foamed Plastics. 
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32.
Tarion warranted a structural related claim where a floor joist was not adequately supported by a beam in accordance with 9.23.9.2. 
Tarion warranted a structural related claim where the end-bearing of a floor joist was not in compliance with 9.23.9.1. 
Tarion warranted a carbon monoxide related claim where the bedrooms were not in compliance with 9.33.4.2. Location of Carbon Monoxide Alarms. 
Tarion warranted a cladding related claim where the installation was not in compliance with 9.27.2.4. Protection of Cladding from Moisture. 
Tarion warranted a claim for a wood column not installed in compliance with 9.17.4.3. Columns in Contact with Concrete. 
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit was not weather-stripped and did not have a self-closing device as per 9.10.13.15.(1) 
Tarion warranted a thermal insulation related claim where the mudroom floor was not insulated as per 9.25.2.1.
Tarion warranted a drainage related claim for a basement slab where the slope was not in compliance with 9.16.3.3. Floor Drains.
Tarion warranted a stair related claim where the risers of an exterior stairs were not in compliance with 9.8.4.1. Dimensions for Risers. 
Tarion warranted a cladding related claim where the brick installation was not in compliance with 9.20.4. Mortar Joints thickness and 9.20.13.8. Required Weep Holes. 
Tarion warranted a guard related claim for a sliding door opening leading to the outside with missing guards. Item not in compliance with 9.8.8.1. Required Guards. 
Tarion warranted a claim related to the insulating value of an exhaust duct passing through an attic. Issue was not in compliance with 9.32.3.10. Ducts
Tarion warranted a cladding related claim where the brick installation was not in compliance with 9.20.8.5. Projection of Masonry Veneer Beyond Supporting Members. 
Tarion warranted a structural related claim where the exterior wall was not laterally braced in accordance with 9.23.10.2.
Tarion warranted an insulation related claim where low thermal resistance levels were identified in the ceiling of a home. Issue not in compliance with 9.25.2. Thermal Insulation requirements. 
Tarion warranted a stair related claim where the risers of an interior stairs were not in compliance with 9.8.4. Step Dimensions. 
Tarion warranted a stair related claim where the treads in interior stairs were not in compliance with 9.8.4.4. Uniformity and Tolerances for Riser, Runs and Treads. 
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32.
Tarion warranted a waterproofing related claim for a shower wall installation not in compliance with 9.29.2. Waterproof Wall Finish. 
Tarion warranted a structural related claim where the columns serving a covered back porch were not in compliance with 9.17.2.1. Location of columns on footings, and 9.23.6.2. Anchorage of Columns and Posts. 
Tarion warranted a claim for exterior wood columns not installed in compliance with 9.17.4.3. Columns in Contact with Concrete. 
Tarion warranted a guard related claim where a guard was missing from a porch. Issue not in compliance with 9.8.8.
Tarion warranted a claim related to the sanitary drainage system where the building's garage level was not in compliance with 7.4.6.4. Protection from Backflow. 
Tarion warranted a claim related to the general performance criteria of doors where the rear double doors were not installed in compliance with 9.7.3.1. 
Tarion warranted a claim related to the general performance criteria of doors where the rear double doors were not installed in compliance with 9.7.3.1.
Tarion warranted a roofing related claim where the downspouts were not in compliance with 9.26.18.2.
Tarion warranted a guard related claim where a deck was built with no guards and in contravention of 9.8.8. 
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits.
Tarion warranted a stair related claim where the risers of an interior stairs were not in compliance with 9.8.4. Step Dimensions. 
Tarion warranted a roofing related claim where the slope of a balcony was not sufficient and allowed for water accumulation at the guard posts' anchorage locations. Issue deemed not in compliance with 9.26.3.1.(4) Slope of Roof Surfaces.   
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit did not have a self-closing device as per 9.10.13.15.(1) 
Tarion warranted a claim related to interior wall finishes where the joints between the tile and the bathtub were not in compliance with 9.29.10.5.
Tarion warranted a claim related to the Control of Rain Water Penetration requirements in the code where the exterior brick wall construction was not in compliance with 9.20.13.8. Required Weep Holes. 
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits.
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits.
Tarion warranted a structural related claim where the floor joists serving a landing were not in compliance with 9.23.9.1. End Bearing for Joists. 
Tarion warranted a claim related to the Control of Rain Water Penetration requirements in the code where the construction of an exterior brick wall was not in compliance with 9.20.13.8. Required Weep Holes. 
Tarion warranted an air barrier related claim where no air barrier was installed between a cold room and the house. Issue not in compliance with 9.25.3. Air Barrier Systems.

2021 OBC Deficiencies

Q3

 

Description of deficiency
Tarion warranted a claim related to a door between an attached garage and the house as not being weatherstripped in accordance with OBC Sentence 9.10.13.15.(1).  
Tarion warranted a claim related to high levels of radon in a home in excess of 220 Bq/m³ in contravention with Sentence 9.13.4.2.(1).  
Tarion warranted an interior guard that was not in accordance with OBC Sentence 9.8.8.2.(1) Loads on Guards  
Tarion warranted a claim with respect to handrails in an exit stair not in accordance with Sentence 3.4.6.5.(11) - 50 mm clearance to the wall.  
Tarion warranted a claim with respect to floor numbers not installed in accordance with OBC Sentences 3.4.6.19. (1) & (2)  
Tarion warranted a claim with respect to a kitchen exhaust duct that did not exhaust directly to the outside required by OBC Sentence 9.32.3.5.(2)  
Tarion warranted a claim with respect to a main entrance door that was not weatherstripped in contravention with OBC Sentence 9.7.3.1.(3).  
Tarion warranted a claim with respect to insufficient support of an HVAC branch duct in contravention of Sentence 6.2.4.3.(7)  
Tarion warranted a claim with respect to a return air duct penetrated by a drain pipe that is not sufficiently sealed in contravention of Sentence 6.2.4.7.(6)  
Tarion warranted a claim with respect to a supply air duct not correctly connected in contravention with Sentence 6.2.4.3.(4).  
Tarion warranted a claim with respect to supply outlets not provided with diffusers in contravention with OBC Sentence 6.2.4.4.(9)  
Tarion warranted a claim with respect to the air barrier separation between the dwelling unit and the attached garage in contravention with OBC Sentence 9.10.9.16.(4)  
Tarion warranted a claim with respect to a concrete slab that did not slope away from the building in contravention with OBC Sentence 9.39.1.4.(5)  
Tarion warranted a claim that there was no flashing behind face brick above a window in contravention of Article 9.20.13.3.  
Tarion warranted a claim that there was insufficient caulking provided between an exterior door and face brick in contravention with OBC Sentences 9.27.4.1.(1) & (3).  
Tarion warranted a claim where there was no caulking provided between a concrete porch and an exterior door jamb in contravention with OBC Sentence 9.20.4.1.(2).  
Tarion warranted a claim that an interior guard did not meet the loading requirements in contravention with OBC Sentence 9.8.8.2.(1).  
Tarion warranted a claim that there was an insufficient air barrier between an attached garage and living space in contravention of OBC Sentence 9.10.9.16.(4)  
Tarion warranted a claim with respect to a door between an attached garage and the house did not self-close in contravention with Sentence 9.10.13.15.(1) & (2).  
Tarion warranted a claim that roof drain scuppers were not provided in contravention with OBC Sentence 7.4.10.4.(3).  
Tarion warranted a claim that there was insufficient caulking provided between a window and face brick in contravention with OBC Sentences 9.27.4.1.(1) & (3).  
Tarion warranted a claim that there was no flashing behind face brick above a porch roof and no weep holes installed in contravention with OBC Articles 9.20.13.3. &  9.20.13.8.  
Tarion warranted a claim that a sump pit cover was not sealed in contravention with OBC 9.25.3.3.(16).  
Tarion warranted a claim that a 150 mm clearance between the ground and wood siding was not provided in contravention of OBC Sentence 9.3.2.9.(7).  
Tarion warranted a claim that there was an insufficient air barrier between an attached garage and living space in contravention of OBC Sentence 9.10.9.16.(4)  
Tarion warranted a claim where an air admittance valve was installed where there was no difficulty in installing a standard vent in contravention with OBC Sentence 7.5.9.2 (1)  
Tarion warranted a claim where a floor joist was cracked to the extent that the floor was sagging in that location in contravention of OBC Div. A, Article 1.2.2.1.  
Tarion warranted a number of claims with respect to openings in fire separations not sealed and penetrated by building services not fire stopped in contravention with OBC Sentences 3.1.8.1(1) and 3.1.9.1.(1).  
Tarion warranted a claim with respect to sprinkler heads not installed in accordance with OBC Sentence 3.2.5.13.(1).  
Tarion warranted a number of claims with respect to a lack of mechanical ventilation in a mechanical room in contravention with Article 6.2.2.1.  
Tarion warranted a number of claims with respect to ventilation and exhaust of a room through a public corridor in contravention with Sentence 6.2.3.9.(4).  
Tarion warranted a claim with respect to the lack of access to a fire damper in contravention with Sentence 3.1.8.9.(5)  
Tarion warranted a claim with respect to a lack of heat in a mechanical room which houses fire protection equipment to ensure that the equipment doesn't freeze in contravention with Article 3.2.5.18.  
Tarion warranted a claim with respect to the lack of a power door operator to a universal toilet room in contravention with Clause 3.8.3.12.(1)(j).  
Tarion warranted a claim with respect to the lack of emergency lighting in a service room in contravention with Sentence 3.2.7.3.(2).  
Tarion warranted a claim with respect to an emergency generator not installed in contravention with Article 3.2.7.9.  
Tarion warranted two claims with respect to floor numbering inside the exit stairs was not raised in contravention with Clause 3.4.6.18.(1)(b).  
Tarion warranted a claim with respect to an exterior wall EIFS system not completed in contravention with Article 5.3.1.1.  
Tarion warranted a claim with respect to a guard on a balcony that would facilitate climbing in contravention with Sentence 3.4.6.5.(8).  
Tarion warranted a claim with respect to guard on a balcony that has an opening greater than 100 mm sphere in contravention with Sentence 3.4.6.5.(5).  
Tarion warranted a claim with respect to a lack of sealant between a window frame and masonry in contravention with OBC Sentence 9.27.4.1.(2).  
Tarion warranted a claim with respect to an interior guard that was in contravention with Sentence 9.8.8.2.(1).  
Tarion warranted a claim with respect to a column that was not anchored to the foundation in contravention with OBC Sentence 9.23.6.2.(1).  
Tarion warranted a claim with respect to undersized wood columns supporting the portion of the structural frame of the building in contravention with OBC Sentence 9.17.4.2.(2)  
Tarion warranted a claim with respect to a door between the dwelling and an attached garage not providing an effective barrier to gas fumes in contravention with OBC Article 9.10.9.16.  
Q4
Description of deficiency
Tarion warranted a claim related to an interior  handrail in a house not being in accordance with OBC Sentence 9.8.7.7.(1).
Tarion warranted a two claims related to a lack of exterior caulking around windows in a house in contravention with Article 9.27.4.1.
TTarion warranted a claim where an exterior guard was required to be installed on a front porch where the difference in height was greater than 600 mm in contravention with OBC Sentence 9.8.8.1.(1)
Tarion warranted a claim with respect to a door leading to an attached garage from the house was not tightly fitted in accordance with Sentence 9.10.13.15.(1).
Tarion warranted a claim with respect to a return air duct that on the 2nd floor to house was also connected to a return air duct on the main floor in contravention with OBC Sentence 6.2.4.7.(7))
Tarion warranted a claim with respect to blocked weep holes to face brick required by OBC Sentence 9.20.13.8.(1)
Tarion warranted a claim with respect to the thickness of mortar joints of face brick being in excess of the tolerances provided in Sentence 9.20.4.1.(2).
Tarion warranted two separate claims with respect to a lack of sealant to provide a sufficient gas barrier between an attached garage and the house in contravention of Sentence 9.10.9.16.(4).
Tarion warranted a claim with respect to an interior stair in a house that exceeded the maximum tolerances for stair risers in  Sentence 9.8.4.4.(1).
Tarion warranted a claim with respect to sill plates in a house that were not leveled in accordance with 9.23.7.2.(1).
Tarion warranted a claim with respect to a vertical fire separation in an attic space between two townhouse units as not having the drywall edges taped in contravention with OBC Sentence 9.10.9.2.(1)
Tarion warranted a claim with respect to floor joists in a house not having the minimum end bearing of 38 mm with OBC Sentence 9.23.9.1.(1).
Tarion warranted a claim with respect to insulation in an attic space in a house as not being uniformly disturbed in contravention with OBC Sentence 9.25.2.3.(1)
Tarion warranted a claim with respect to a door between the dwelling and an attached garage not providing an effective barrier to gas fumes in contravention with OBC Sentence 9.10.13.15.(1).
Tarion warranted a claim with respect to a door between the dwelling and an attached garage not providing an effective barrier to gas fumes in contravention with OBC Sentence 9.10.13.15.(1).
Tarion warranted a claim with respect to the construction of an exterior wooden deck at the rear of a home where the following deficiencies were found: Stairs serving the deck exceeded the maximum tolerances for stair risers in  OBC Sentence 9.8.4.4.(1). Beams supporting the deck did not have an even and level bearing in accordance with OBC Sentence 9.23.8.1.(1), Nailing of the deck materials did not conform to OBC Table 9.23.3.4., and The guard to the deck was not constructed in accordance with MMAH Supplementary Standard SB-7 of the OBC.
Tarion warranted a claim with respect to a lack of weep holes to face brick on a house required by OBC Sentence 9.20.13.8.(1)
Tarion warranted a claim that the top of a foundation wall to a house was not the minimum of 150 mm above the finished grade in OBC Sentence 9.15.4.6.(1)
Tarion warranted a claim with respect to a concrete slab on a house that did not drain away from the house in contravention with OBC Sentence 9.39.1.4.(5)
Tarion warranted a claim with respect to insufficient ventilation provided to a cold room in a house in contravention with OBC Table 9.32.2.1.
Tarion warranted a claim where exterior intake and exhaust vents to a house were not separated from one another in contravention with OBC Article 9.32.3.12.
Tarion warranted a claim that the top of a foundation wall to a house was not the minimum of 150 mm above the finished grade in OBC Sentence 9.15.4.6.(1)
Tarion warranted a two separate claims that the top of a foundation wall to two homes were not the minimum of 150 mm above the finished grade in OBC Sentence 9.15.4.6.(1)
Tarion warranted a claim with respect to a lack of weep holes to face brick on a house required by OBC Sentence 9.20.13.8.(1)
Tarion warranted a claim where exterior intake and exhaust vents to a house were not separated from one another in contravention with OBC Article 9.32.3.12.
Tarion warranted a claim with respect to an exterior stair serving an attached garage to a house had a riser in excess of 200 mm in contravention with OBC Table 9.8.4.1.
Tarion warranted a claim with respect to a lack of weep holes to face brick on a house required by OBC Sentence 9.20.13.8.(1)
Tarion warranted two claims with respect a deficient fire separation between two semi-detached homes as being not in accordance with OBC Sentences 9.10.9.2.(1) & (2).
Tarion warranted a claim with respect to a lack of an air barrier behind a gas fireplace in a house that was in contravention of OBC Article 9.25.3.3.
Tarion warranted a number of claims with respect to block wall fire separations that have cracks in them that were not sealed to maintain the integrity of the fire separations in contravention with OBC Sentence 3.1.8.1(1).
Tarion warranted a two claims with respect to an interior stairs in these homes that exceeded the maximum tolerances for stair risers in  Sentence 9.8.4.4.(1).
Tarion warranted a claim with respect to a home where there was no metal flashing with drip edge installed between a stone veneer and metal cladding in contravention with OBC Article 9.27.1.1.