Ontario Building Code Warranted by Tarion
By law, all new homes in Ontario built by a licensed vendor or builder come with a statutory warranty under the Ontario New Home Warranties Plan Act (ONHWPA). This statutory warranty protection follows the home and is valid for seven years from the original date of possession, regardless of who owns the home. Coverage for Ontario Building Code (OBC) violations is as follows:
- Violations of the OBC are covered for one year from the original date of possession
- Violations of the OBC related to health and safety are covered for two years from the original date of possession
In an effort to improve coordination with municipal building departments, Tarion will now be posting on a quarterly basis a summary of any claims that were deemed warranted and were related to the OBC. This information is being provided to allow building departments an opportunity to better understand the issues that are brought to Tarion's attention after an occupancy permit is granted.
To view the claims by quarter, click on the accordion menus below. If you have any questions regarding this information, please email municipalinfo@tarion.com
Individual emails will go out to municipal building departments on a quarterly basis with information on the warranted OBC deficiencies, if any, in that municipality. To facilitate this outreach, please complete this form with the contact information for the person who should receive this emailed information.
2024 OBC Deficiencies
Q1
Description of OBC Deficiency |
---|
Tarion warranted a Carbon Monoxide Alarm not in compliance with 9.33.4. Carbon Monoxide Alarms. |
Tarion warranted columns not in compliance with 9.17.4.3. Columns in Contact with Concrete. |
Tarion warranted missing weep holes not in compliance 9.20.13.8. Required Weep Holes. |
Tarion warranted an attic hatch not in compliance with 9.25.3.3. Continuity of the Air Barrier System. |
Tarion warranted dryer ventilation ducts not in compliance with 9.32.1.4. Venting of Laundry-Drying Equipment. |
Tarion warranted guards not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted guards not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted an exhaust not in compliance with 9.32.3.5. Supplemental Exhaust. |
Tarion warranted gas proofing not in compliance with 9.10.9.16. Separation of Storage Garages. |
Tarion warranted insulation not in compliance with 9.25.2.3. Installation of Thermal Insulation. |
Tarion warranted a duct not in compliance with 9.32.3.10. Ducts. |
Tarion warranted brick veneer not in compliance with 9.20.12.3. Corbelling for Masonry Veneer. |
Tarion warranted tiles not in compliance with 9.29.10.4 Moisture Resistant Backing. |
Tarion warranted a missing guard not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted a sump pump not in compliance with 9.25.3.3. Continuity of the Barrier System. |
Tarion warranted a landing not in compliance with 9.8.6.2. Required Landings. |
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted a handrail not in compliance with 9.8.7.2. Continuity of Handrails. |
Tarion warranted sealant not in compliance with 9.27.4.1. Required Sealants. |
Tarion warranted weather stripping not in compliance with 9.7.3. Performance of Windows, Doors and Skylights. |
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads. |
Tarion warranted a door not in compliance with 9.10.9.16. Separation of Storage Garages. |
Q2
Description of OBC Deficiency |
---|
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads. |
Tarion warranted grade not in compliance with 9.15.4.6. Extension Above Ground Level. |
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads. |
Tarion warranted a staircase not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers, Runs and Treads. |
Tarion warranted a handrail not in compliance with 9.8.7.7. Design and Attachment of Handrails. |
Tarion warranted masonry not in compliance with 9.20.12.3. Corbelling for Masonry Veneer. |
Tarion warranted handrails not in compliance with 9.8.7.7. Design and Attachment of Handrails. |
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted flashing not in compliance with 9.20.13.5. Flashing for Weep Holes in Masonry Veneer. |
Tarion warranted a garage floor not in compliance with 9.35.2.2. Garage Floor. |
Tarion warranted fire sealant not in compliance with 3.1.9.1. Fire Stops. |
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of the Air Barrier System. |
Tarion warranted spray foam not in compliance with 9.10.17.10. Protection of Foamed Plastics. |
Tarion warranted stairs not in compliance with 9.8.4.4. Uniformity and Tolerance for Risers, Runs and Treads. |
Tarion warranted a trap not in compliance with 7.4.5.5. Trap Seals. |
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. |
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. |
Tarion warranted dampers not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. |
Tarion warranted guards not in compliance with 9.8.8.5. Opening in Guards. |
Tarion warranted an air barrier not in compliance with 9.10.9.16. Separation of Storage Garages. |
Tarion warranted a door not in compliance with 9.10.13.15. Doors Between Garages and Houses or Dwelling Units. |
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of the Air Barrier System. |
Tarion warranted a backflow preventer not in compliance with 7.6.2.2. Back-Siphonage. |
Q3
Description of OBC Deficiency |
---|
Tarion warranted guards not in compliance with 9.8.8.1 ‘Required Guards’ |
Tarion warranted joints between tiles and bathtub not in compliance with 9.29.10.5. ‘Joints between tiles and Bathtub’ |
Tarion warranted an air barrier not in compliance with 9.25.3 "Continuity of the Air Barrier System" |
Tarion warranted heating design and installation not in compliance with 9.33.1.1. ‘Design and Installation Requirements’ |
Tarion warranted steps not in compliance with 9.8.4.1 ‘Dimensions for Risers’ |
Tarion warranted weep holes not in compliance with 9.20.13.8.(1) ‘Required Weep Holes’ |
Tarion warranted clearance from grade not in compliance with 9.15.4.6.(1) ‘Extension Above Grade Level’ |
Tarion warranted spindles not in compliance with 9.8.8.5 (3) ‘Openings in Guards’ |
Tarion warranted roof drainage not in compliance with 5.6.2.2.(3) ‘Accumulation and Disposal’ |
Tarion warranted fire ratings not in compliance with 9.10.3.1 ‘Fire-Resistance and Fire Protection Ratings’ |
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’ |
Tarion warranted entrance lighting not in compliance with 9.34.2.1 ‘Lighting of Entrances’ |
Tarion warranted lateral support not in compliance with 9.17.2.2.(1) ‘Lateral support’ |
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’ |
Tarion warranted a shut-off valve not in compliance with 7.6.1.3. ‘Control and Shut-off Valves’ |
Tarion warranted an air barrier system not in compliance with 9.25.3. ‘Continuity of the Air Barrier System’ |
Tarion warranted a pool deck not in compliance with 3.11.3.1.(24) ‘Pool and Pool Design and Construction Requirements |
Tarion warranted a stud wall not in compliance with 3.8.3.13(2)(e) ‘Stud Wall Reinforcement’ |
Tarion warranted entry door not in compliance with 3.8.1.3. ‘Barrier-Free Path of Travel’ |
Tarion warranted lighting not in compliance with 12.2.4.1. ‘Motion Sensors’ |
Tarion warranted lighting not in compliance with 12.2.4.1. ‘Motion Sensors’ |
Tarion warranted a toilet not in compliance with 3.8.3.8. ‘Washroom to be Barrier-Free’ |
Tarion warranted a door not in compliance with 3.8.3.3. ‘Doorways and Doors’ |
Tarion warranted a door not in compliance with 3.8.3.3. ‘Doorways and Doors’. |
Tarion warranted a water closet not in compliance with 3.8.3.8 ‘Water Closet Stalls and Enclosures’ |
Tarion warranted backflow prevention not in compliance with 7.6.2.2. ‘Back-Siphonage’ |
Tarion warranted a door not in compliance with 9.10.13.15 ‘Other Requirements for Windows and Doors’ |
Tarion warranted a guard not in compliance with 9.8.8.5 ‘Openings of Guards’ |
Tarion warranted a sump pit not in compliance with 9.25.3.3. ‘Sump Pits’ |
Tarion warranted a window height not in compliance with 9.15.4.6 ‘Extension Above Ground Level’ |
Tarion warranted the first plane of protection not in compliance with 9.27.2.3 ‘First and Second Planes of Protection’ |
Tarion warranted a door not in compliance with 9.7.3.1 ‘Performance of Windows, Doors and Skylights’ |
2023 OBC Deficiencies
Q1
Description of OBC Deficiency |
---|
Tarion warranted a stair-related claim where the front steps to the house were not in compliance with 9.8.4.4.(1). Uniformity and Tolerances for Riser, Runs and Treads. |
Tarion warranted a claim related to a factory-built fireplace where its installation was not in compliance with 9.22.8.1. Conformance to Standard CAN/ULC-S610-M. |
Tarion warranted a cladding related claim where the first plane of protection for the exterior wall was not in compliance with 9.27.2.3. First and Second Planes of Protection. |
Tarion warranted a drainage related claim where the foundation wall was not in compliance with 9.14.2.1. Foundation Wall Drainage. |
Tarion warranted a claim related to missing guards and missing handrails from a rear deck and stairs (serving deck). These items are not in compliance with 9.8.8.1. Required Guards, and 9.8.7.1. Required Handrails. |
Tarion warranted a mechanical ventilation related claim where the air intake for the furnace and water heater were not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings. |
Tarion warranted a thermal insulation related claim where the installation in the basement level was not in compliance with 9.25.2.3. Installation of Thermal Insulation. |
Tarion warranted a cladding related claim where the brick veneer installed was not in compliance with 9.20.12.3. Corbelling for Masonry Veneer. |
Tarion warranted a heating related claim where the installed system was not able to maintain an indoor temperature in accordance with 9.33.3.1. Indoor Design Temperatures. |
Tarion warranted a guard related claim where the front porch of the house was not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted an electrical related claim where the utility room was not in compliance with 9.34.2.2. Lighting Outlets in Houses and Dwelling Units. |
Tarion warranted a cladding related claim where the vents penetrating the cladding were not sealed in accordance with 9.27.4.1. Required Sealants. |
Tarion warranted a claim related to wall tile finishes where the joints between the washroom tiles were not in compliance with 9.29.10.5. Joints Between Tiles and Bathtub. |
Tarion warranted a plumbing related claim where the water pipe was not in compliance with 7.3.4. Support of Piping. |
Q2
Description of OBC Deficiency |
---|
Tarion warranted a handrail not in compliance with 9.8.7.7. Design and Attachment of Handrails. |
Tarion warranted insulation not in compliance with 9.25.2.1. Required Insulation. |
Tarion warranted intake and exhaust pipes not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings. |
Tarion warranted an exterior step not in compliance with 9.8.4.4. Uniformity and Tolerances for Riders, Runs and Treads. |
Tarion warranted an exterior door not in compliance with 9.25.1.1. Heat Transfer, Air Leakage and Condensation Control - Scope and Application. |
Tarion warranted an air barrier not in compliance with 9.10.9.16. Separation of Storage Garages. |
Tarion warranted a balcony guardrail and not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted tread depth not in compliance with Table 9.8.4.1., 9.8.4.4. and 9.8.2.2. Dimensions for Risers, Uniformity and Tolerances for Risers, Runs and Treads, and Height Over Stairs. |
Tarion warranted rise of a step not in compliance with 9.8.4.1. Dimensions for Risers. |
Tarion warranted radon mitigation not in compliance with 9.13.4.1. and 9.13.4.2. Soil Gas Control. |
Tarion warranted a foundation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted a self-closer device not in compliance with 9.10.13.10. Self-Closing Devices. |
Tarion warranted a window installation not in compliance with 9.7.6.2. and 9.25.3.3. Sealants, Trim and Flashing and Continuity of Air Barrier System. |
Tarion warranted an air barrier not in compliance with 9.25.3.3. Continuity of Air Barrier System. |
Tarion warranted wood framing not in compliance with 9.27.1.1. Cladding – General. |
Tarion warranted vapour barrier not in compliance with 9.13.2.5. Moisture Protection for Interior Finishes. |
Tarion warranted an air barrier not in compliance with 9.10.9.16. and 9.25.3.1. Separation of Storage Garages and Required Barrier to Air Leakage. |
Tarion warranted weep holes within the masonry not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted an HVAC duct not in compliance with 6.2.4.3. Construction and Installation of Ducts and Plenums. |
Tarion warranted framing not in compliance with 9.23.10.1 and 9.23.12.1. Stud Size and Spacing and Openings in Non-Loadbearing Walls. |
Tarion warranted a basement foundation that had a form tie not in compliance with 9.15.6.3. Form Ties. |
Tarion warranted weep holes within the masonry not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted a guard not in compliance with 9.8.8.2. Loads on Guards. |
Tarion warranted a steel lintel not in compliance with 9.20.5.2. Lintels or Arches. |
Tarion warranted vent opening not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings. |
Tarion warranted an air barrier not in compliance with 9.25.3.1. and 9.25.3.3. Required Barrier to Air Leakage and Continuity of the Air Barrier System. |
Tarion warranted a landing not in compliance with 9.8.6.3. Dimensions of Landings. |
Q3
Description of OBC Deficiency |
---|
Tarion warranted front porch guard rails not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted primary entrance doors not in compliance with 9.7.2.1. Entrance Door. |
Tarion warranted Basement - Stairs - Staircase/Steps - Stairs leading to basement not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers and Treads. |
Tarion warranted hot water heater input and exhaust pipes not in compliance with 9.32.3.12. Outdoor Intake and Exhaust Openings. |
Tarion warranted stairs not in compliance with 9.8.4.1. Uniformity and Tolerances for Risers and Treads. |
Tarion warranted man doors to garages not in compliance with 9.10.13.15 (1). Doors Between Garages and Dwelling Units |
Tarion warranted weeping holes not in compliance with 9.20.13.8 (1)(b). Required Weep Holes. |
Tarion warranted drywall not in compliance with 9.10.9.16.(4)(a). Separation of Storage Garages |
Tarion warranted hot water supply; not in compliance with 9.31.3.2(2). Required Connections. |
Tarion warranted door frame not in compliance with 9.10.9.16.(4)(a). Separation of Storage Garages |
Tarion warranted a deck railing not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted electrical wires not in compliance with 9.34.1.5 (1). Wiring and Cables. |
Tarion warranted steps not in compliance with 9.8.9.2 (1). Exterior Concrete Stairs. |
Tarion warranted a sump pump pit not in compliance with 9.25.3.3.(16). Continuity of Air Barrier. |
Tarion warranted a floor drain not in compliance 9.31.4.4.(1). Floor Drains. |
Tarion warranted steps not in compliance with 9.8.1.2. (1). Exit Stairs, Ramps and Landings. |
Tarion warranted steps not in compliance with 9.8.1.2. (1). Exit Stairs, Ramps and Landings. |
Tarion warranted electrical wires not in compliance with 9.34.1.5 (1). Wiring and Cables. |
Tarion warranted a front door not in compliance with 9.7.2.1. Entrance Door. |
Tarion warranted support timbers not in compliance with 9.23.5.3. Wall Studs. |
Q4
Description of OBC deficiency |
---|
Tarion warranted steps not in compliance with 9.8.4.4. Uniformity and Tolerances for Risers and Treads. |
Tarion warranted a basement floor slab not in compliance with 9.23.2.3. Protection from Dampness. |
Tarion warranted a staircase not in compliance with 9.8.2.1. Stair Width. |
Tarion warranted trimmer joists not in compliance with 9.23.9.6. Trimmer Joists. |
Tarion warranted framing not in compliance with 9.23.9.4. Strapping and Bridging. |
Tarion warranted window openings not in compliance with 9.23.12.2. Openings in Load Bearing Walls. |
Tarion warranted floor joists not in compliance with 9.23.9.4. Strapping and Bridging. |
Tarion warranted window openings not in compliance with 9.23.12.2. Openings in Load Bearing Walls. |
Tarion warranted a door opening not in compliance with 9.23.9.6. Trimmer Joists. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted weep holes not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted an exterior door not in compliance with 9.25.3.3 and 9.25.4.1. Continuity of the Air Barrier System and Required Barrier to Vapour Diffusion. |
Tarion warranted a vent not in compliance with 9.19.1.2. Vent Requirements. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted a door not in compliance with 9.10.13.15. Doors Between Garages and Houses or Dwelling Units. |
Tarion warranted a roof not in compliance with 9.26.3.1. Slope. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted insulation not in compliance with 9.25. Heat Transfer, Air Leakage and Condensation Control. |
Tarion warranted brick masonry not in compliance with 9.20.12.3. Corbelling for Cavity Walls. |
Tarion warranted a roof not in compliance with 9.26.3.1. Slope. |
Tarion Warranted a guard not in compliance with 9.8.8.4. Guards for Floors and Ramps in Garages. |
Tarion warranted an HVAC vent not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. |
Tarion warranted a door not in compliance with 3.1.8.5. Installation of Closures. |
Tarion warranted a staircase and landing not in compliance with 3.4.6.3. Maximum Vertical Rise of Stair Flights and Required Landings. |
Tarion warranted ventilation not in compliance with 6.2.2.3 and 6.2.3.8. Ventilation of Storage and Repair Garages and Exhaust Ducts and Outlets. |
Tarion warranted staircase levels; not in compliance with 3.4.6.8. Treads and Risers. |
Tarion warranted an exit not in compliance with 3.4.3.5. Headroom Clearance. |
Tarion warranted a landing not in compliance with 3.4.6.4. Dimensions of Landings. |
Tarion warranted vent covers missing to open and close vents; not in compliance with 6.2.4.6. Adjustable Dampers and Balance Stops. |
Tarion warranted a garage door not in compliance with 9.10.13.15. Doors Between Garages and Houses or Dwelling Units. |
Tarion warranted a staircase and handrail not in compliance with 9.8.4.5A. and 9.8.7.4. Spiral Stairs and Height of Handrails. |
Tarion warranted a foundation not in compliance with 9.15.4.6. Extension Above Ground Level. |
2022 OBC Deficiencies
Q1
|
Q2
|
Q3
|
Q4
Description of OBC Deficiency |
---|
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32. |
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit was not tight-fitting as per 9.10.13.15.(1) |
Tarion warranted a handrail related claim where its construction was not in compliance with 9.8.7.2. Continuity of Handrails. |
Tarion warranted a guard related claim for the basement stairs where the guards were not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted a ventilation related claim where the kitchen exhaust was not in compliance with 9.32.3. |
Tarion warranted a fire protection related claim for the ICF foundation wall not in compliance with 9.10.17.10. Protection to Foamed Plastics. |
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32. |
Tarion warranted a structural related claim where a floor joist was not adequately supported by a beam in accordance with 9.23.9.2. |
Tarion warranted a structural related claim where the end-bearing of a floor joist was not in compliance with 9.23.9.1. |
Tarion warranted a carbon monoxide related claim where the bedrooms were not in compliance with 9.33.4.2. Location of Carbon Monoxide Alarms. |
Tarion warranted a cladding related claim where the installation was not in compliance with 9.27.2.4. Protection of Cladding from Moisture. |
Tarion warranted a claim for a wood column not installed in compliance with 9.17.4.3. Columns in Contact with Concrete. |
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit was not weather-stripped and did not have a self-closing device as per 9.10.13.15.(1) |
Tarion warranted a thermal insulation related claim where the mudroom floor was not insulated as per 9.25.2.1. |
Tarion warranted a drainage related claim for a basement slab where the slope was not in compliance with 9.16.3.3. Floor Drains. |
Tarion warranted a stair related claim where the risers of an exterior stairs were not in compliance with 9.8.4.1. Dimensions for Risers. |
Tarion warranted a cladding related claim where the brick installation was not in compliance with 9.20.4. Mortar Joints thickness and 9.20.13.8. Required Weep Holes. |
Tarion warranted a guard related claim for a sliding door opening leading to the outside with missing guards. Item not in compliance with 9.8.8.1. Required Guards. |
Tarion warranted a claim related to the insulating value of an exhaust duct passing through an attic. Issue was not in compliance with 9.32.3.10. Ducts |
Tarion warranted a cladding related claim where the brick installation was not in compliance with 9.20.8.5. Projection of Masonry Veneer Beyond Supporting Members. |
Tarion warranted a structural related claim where the exterior wall was not laterally braced in accordance with 9.23.10.2. |
Tarion warranted an insulation related claim where low thermal resistance levels were identified in the ceiling of a home. Issue not in compliance with 9.25.2. Thermal Insulation requirements. |
Tarion warranted a stair related claim where the risers of an interior stairs were not in compliance with 9.8.4. Step Dimensions. |
Tarion warranted a stair related claim where the treads in interior stairs were not in compliance with 9.8.4.4. Uniformity and Tolerances for Riser, Runs and Treads. |
Tarion warranted a ventilation related claim where the cold room in the basement was not adequately ventilated as per 9.32. |
Tarion warranted a waterproofing related claim for a shower wall installation not in compliance with 9.29.2. Waterproof Wall Finish. |
Tarion warranted a structural related claim where the columns serving a covered back porch were not in compliance with 9.17.2.1. Location of columns on footings, and 9.23.6.2. Anchorage of Columns and Posts. |
Tarion warranted a claim for exterior wood columns not installed in compliance with 9.17.4.3. Columns in Contact with Concrete. |
Tarion warranted a guard related claim where a guard was missing from a porch. Issue not in compliance with 9.8.8. |
Tarion warranted a claim related to the sanitary drainage system where the building's garage level was not in compliance with 7.4.6.4. Protection from Backflow. |
Tarion warranted a claim related to the general performance criteria of doors where the rear double doors were not installed in compliance with 9.7.3.1. |
Tarion warranted a claim related to the general performance criteria of doors where the rear double doors were not installed in compliance with 9.7.3.1. |
Tarion warranted a roofing related claim where the downspouts were not in compliance with 9.26.18.2. |
Tarion warranted a guard related claim where a deck was built with no guards and in contravention of 9.8.8. |
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits. |
Tarion warranted a stair related claim where the risers of an interior stairs were not in compliance with 9.8.4. Step Dimensions. |
Tarion warranted a roofing related claim where the slope of a balcony was not sufficient and allowed for water accumulation at the guard posts' anchorage locations. Issue deemed not in compliance with 9.26.3.1.(4) Slope of Roof Surfaces. |
Tarion warranted a fire separation related claim where the door between the garage and the dwelling unit did not have a self-closing device as per 9.10.13.15.(1) |
Tarion warranted a claim related to interior wall finishes where the joints between the tile and the bathtub were not in compliance with 9.29.10.5. |
Tarion warranted a claim related to the Control of Rain Water Penetration requirements in the code where the exterior brick wall construction was not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits. |
Tarion warranted a drainage disposal related claim where the sump pit cover was not in compliance with 9.14.5.2. Sump Pits. |
Tarion warranted a structural related claim where the floor joists serving a landing were not in compliance with 9.23.9.1. End Bearing for Joists. |
Tarion warranted a claim related to the Control of Rain Water Penetration requirements in the code where the construction of an exterior brick wall was not in compliance with 9.20.13.8. Required Weep Holes. |
Tarion warranted an air barrier related claim where no air barrier was installed between a cold room and the house. Issue not in compliance with 9.25.3. Air Barrier Systems. |
2021 OBC Deficiencies
Q3
|
Q4
|